6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 661 -
Signal Number
Signal Name
Description
510001 8101141DD0
SPOS20_FEX_BO
SPOS20 operate (OFF) command for Binary Output.
(v) Setting names
Note: The xx of SPOSxx represents the SPOS function number. (e.g., if the SPOS03
is considered, the xx is equal to 03. The suffix xx can be represented from
01 to 20.)
Table 4.1-28 Settings for Binary input signals in SPOSxx
Setting Name
Description
Default
Setting item or value
SPOSxx-EN
Activate monitoring function of SPOS01-20
On
Off / On
SPOSxx-NOPSG
BI position for SPOS01-20
*none
BI signal
SPOSxx-SPPEN
Activate event suppression for SPOS01-20
On
Off / On
SPOS-NELD
Number of change to lock status
10
0~99
SPOS-TELD
Time to lock status( sliding window )
10[sec]
1~99[sec]
SPOS-TELR
Time to unlock status( sliding window )
10[sec]
1~99[sec]
Table 4.1-29 Settings for health check function in SPOSxx
Setting Name
Description
Default
Setting item or value
SPOSxx-SLBORD
Select BO signal (BO*-RB) from signal list
*user-preferred
BO readback signal
SPOSxx-OEXBORD
Select BO signal (BO*-RB) from signal list
*user-preferred
BO readback signal
SPOSxx-FEXBORD
Select BO signal (BO*-RB) from signal list
*user-preferred
BO readback signal