6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 664 -
Table 4.1-30 Mapping signals for SPCSO object
Object_reference
Attribute
Type
FC
Signal Number
Signal Name
Ctrl/GGIO1501$SPCSO$origin
orCat
orCategory
ST
510001 3001011008
SPOS01_ORCAT
Ctrl/GGIO1501$SPCSO$origin
orIdent
Octet64
ST
510001 6A01011009
SPOS01_ORIDENT
Ctrl/GGIO1501$SPCSO
stVal
BOOLEAN
ST
510001 0001011001
SPOS01_STATE
Ctrl/GGIO1501$SPCSO
q
Quality
ST
510001 3101011005
SPOS01_QUALITY
Ctrl/GGIO1501$SPCSO
t
Timestamp
ST
510001 9001011006
SPOS01_TIMESTAMP
Ctrl/GGIO1501$SPCSO
stSeld
BOOLEAN
ST
510001 0001011D90
SPOS01_STD_RPT
Note: Status (ST) is defined in the function constraint (FC) of the IEC 61850 standard.
Drag and drop
Figure 4.1-43 ocCat attribute mapped for SPCSO object of GGIO1501
(iii) Mapping input data
The SPOS01 function can receive three commands select, operate, and cancel. Thus, the user
should map the input-point DEV01_CONTROL_REQto the IEC 61850 communication. Table
4.1-31 shows the input-point DEV01_CONTROL_REQ and the Object reference
Ctrl/GGIO1501$SPCSO; the user should map the input point to the Object reference having
attributes CO and CF. Figure 4.1-44 shows how to map a signal.