- 664 -
Table 4.1-30 Mapping signals for SPCSO object
Ctrl/GGIO1501$SPCSO$origin
Ctrl/GGIO1501$SPCSO$origin
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
Figure 4.1-43 ocCat attribute mapped for SPCSO object of GGIO1501
(iii) Mapping input data
The SPOS01 function can receive three commands “select, operate, and cancel”. Thus, the user
should map the input-point “DEV01_CONTROL_REQ” to the IEC 61850 communication. Table
4.1-31 shows the input-point “DEV01_CONTROL_REQ” and the Object reference
“Ctrl/GGIO1501$SPCSO”; the user should map the input point to the Object reference having
attributes CO and CF†. Figure 4.1-44 shows how to map a signal.