2.3.2 Check relay characteristic (EFD)
To remove unnecessary operations in the DIFGL function, a check relay are accommodated;
consequently, the operation of the DIFGL function is possible during the check relay being in
operation. Figure 2.3-4 shows the check relay and its logic.
EFD-
DIFGL
8000011C23
&
DIFGLFS-OP
To DIFGL main logic
ADD.DIFGLFS
820001EBB0
S 1
R
1
8000011B60
On
DIFGLFS-FED-EN
8200011BB0
1
Off
DIFGLFS-EN
8000011B23
DIFGL#1
1
DIFGL#2
1
Figure 2.3-4 Check relay logic
(i) Earth-fault-current-change detection element (EFD-DIFGL)
Figure 2.3-5 shows a current vector (I
M
) measured at the present and a pre-current vector (I
N
)
measured at one sampling cycle ago. When the magnitude of difference between (I
s
) is larger
than a setting, the operation the EFD-DIFGL element is introduced. The EFD-DIFGL element
is expressed by the following equation:
(2.3-8)
where I
s
is referred in order to determine the operation of the EFD-DIFGL element; the
user can set the value using setting [EFD-DIFGL], which is applied to adjust the decision point
for the operation. The user can set the value among 0.05 to 0.20A when 1A rating is set for
the VCT module. When 5A rating is set for the VCT module, the setting value is chosen among
0.25 to 1.00A.
Figure 2.3-5 Current change I
s
detected by I
M
and I
N
Note: One sampling cycle is discussed later.
Note: For the rating and the VCT module, see Chapter
Technical description:
I
s
I
M
I
N