6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 674 -
(ii) Receiving “select command Open” from the remote-end
Figure 4.2-3 outlines the reception of the select command Open from the remote-end.
Signal reception
IEC61850
Select command Open from the remote-end
Signal output
Select
decision
Success
Failed
Select logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Closing from the remote-end
Select command Closing from the local-end
Select command Open from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Figure 4.2-3 Outline of select command for Open
Input point required mapping
Figure 4.2-4 shows the select logic when a Select command (Remote-Open-Control) signal is
applied to the DPSY01 function. The input-point DEV01_CONTROL_REQ is used for the
reception of the select command (Remote-Open-Control)” signal.
DPSY01_FSL_BO_FLG
(511001 8A02011DC4)
DPSY01 function (Function ID: 511001)
DEV01_CONTROL_REQ
Command Remote-Open-Control
ILK condition (“Open”) passed
Either SBO mode or DIR mode
(e.g., “ctlmodel” in IEC61850*)
In SBO operate
In DIR operate
Select Failed
511001_7002016D08
DPSY01-Open
To BO connection
Input
Output
Selection logic in DPSY01
0.1s
0
t
0.6s
0
t
&
&
&
&
&
Select success
Automatic sequence control function (ASEQ)§ in progress
ASEQ_MULTI_SEL
Select condition
1
Select command
with ILK condition
Operate command
with ILK condition
Select command
without ILK condition
Operate command
without ILK condition
For SBO operation
For DIR operation
To Wait for a command
For DIR operation
For SBO operation
Figure 4.2-4 Select ‘Open’ from the remote-end in DPSY01
††
Note: The ILK function can provide the operation criteria for Open”.
Note: Aselect condition signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
§Note: An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPSY01 operation is blocked for the ASEQ function when