- 679 -
DPSY01 function (Function ID: 511001)
Signals from user-PLC logic
Closing-control command requiring ILK† and synchro
checks (PLC#1 connection point)
Operate command with ILK†
condition & synchro-checking
For DIR operation (PLC#1)
Closing-control command requiring synchro check
(PLC#2 connection point)
Operate command with
synchro-checking
For DIR operation (PLC#2)
ILK condition (“Closing”) passed
Closing-control command requiring ILK† check
(PLC#3 connection point)
Operate command with ILK†
condition
For DIR operation (PLC#3)
Closing-control command with no check
(PLC#4 connection point)
Operate command without
condition
For DIR operation (PLC#4)
DPSY01_OSL_BO_FLG”
(511001 8602011DC6)
SYNC01-SLD_VCS
(560001 840B011F58)
To “Wait for a next
command”
Figure 4.2-10 Select ‘Closing’ using the PLC function in DPSY01
††
††
Note: To identify the input and output signals of the DPSY02 logic, see Table 4.2-3 and
Table 4.2-10.
†Note: The Software interlocking (ILK) function can provide the operation criteria for
“Closing”. The ILK function is discussed separately; note that the operation
criteria is defined in the ILK function itself (i.e., the user cannot set the
condition).
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
§§
Note: A timer is provided to determine a failure to operate. The maximum value of the
settings [SYNC01_TLRDIDRLI] or [SYNC01_TDRDI] is used for the decision time.
For more information on settings, see the SYNDIF function.
Output signal to BO
The DPSY01 function, in Figure 4.2-10, can issue a “Select success” signal at the output-point
“DPSY01_OSL_BO_CSF”
1
.
1
Note: The signal “DPSY01_OSL_BO_CSF” is the same signal as that shown in Figure
4.2-2.