EasyManua.ls Logo

Toshiba GR200 Series - (i) Receiving “change value for counter” from the remote end; (i)-1 Mapping of Input point required; (i)-2 Output signal to BO; (ii) Receiving “change value for counter” from the local-end

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 707 -
(i) Receiving “change value for counter” from the remote end
Mapping of Input point required
Figure 4.2-34 depicts the logic when a change value for counter command is received at the
DPSY01 logic. With regard to a three-phase counter, the input-point
“DEV01_3PH_CONTROL_REQ” is used. With regard to a phase-A counter, the input-point
“DEV01_APH_CONTROL_REQ” is used. For phase-B and phase-C, the input-points
“DEV01_BPH_CONTROL_REQ” and “DEV01_CPH_CONTROL_REQ” are used.
DPSY01 function (Function ID: 511001)
Operate Command
DEV01_3PH_REQ
Command change value for counter
511001_7002016D09
&
DPSY01_SLD_CSCN
(511001 8A02011F88)
Input
Output
Operate logic in DPSY01
Operate condition
Figure 4.2-34 Change counter value for three-phase
with operation from the remote-end in
DPSY01
Note: The “operate condition signal is provided from the operate condition logic shown
in Figure 4.2-36.
Note: The user can apply other counter change commands for phase-A, -B, and C as
shown in Table 4.2-24. The resultant signals for the DPSY02 logic are shown in
Table 4.2-25.
Output signal to BO
The DPSY01 function can issue a Resultsignal at output point DPSY01_SLD_CSCN”. The
counter values are issued at points “DPSY01_CNT_VAL", “DPSY01A_CNT_VAL",
“DPSY01B_CNT_VAL", and “DPSY01C_CNT_VAL".
(ii) Receiving “change value for counter” from the local-end
Input signal from the front panel
Figure 4.2-35 depicts the logic when a change value for counter command is provided in the
DPSY01 function. The command is provided from the sub-menu (see Figure 4.2-33).
DPSY01 function (Function ID: 511001)
DPSY01_SLD_CSCN
(511001 8A02011F88)
Input
Output
Operate logic in DPYS01
Command Change value
Figure 4.2-35 Changing counter value by operation from the front panel in DPSY01
Output signal to BO

Table of Contents

Related product manuals