EasyManua.ls Logo

Toshiba GR200 Series - (iii) Operate condition for the counter

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 708 -
The DPSY01 function can issue a “Result” signal at the output point DPSY01_SLD_CSCN”.
(iii) Operate condition for the counter
Figure 4.2-36 illustrates the operate condition logic. The DPSY01 function can determine an
operate-condition using a signal received from Control hierarchy”. The Control hierarchy
condition is provided by user-programmed PLC logic (i.e., 43R/L); the user must connect the
control-hierarchy with the DPSY01 function using connection point DPSY01IN_TMP_47 (see
Table 4.2-26).
Operate condition
To counter logic
From Control hierarchy
DPSY01IN_TMP_47
511001 800201ED5A
&
1
DPSY01 function (Function ID: 511001)
Detection of serious errors
CBK_STATE
Command blocking*1
Double Command Blocking detected*2
Other devices traveling detected*3
DCB RCV OR
Traveling OR
SERI_ERR
Unmatched condition detected *4
= DPSY01_SC_ST_ERR
From CMNCTRL
Figure 4.2-36 Operate condition logic for changing the counter in DPSY01
1
Note: “Command Blocking” disables all operation except for its own; the “Command
Blocking” function is initiated by the status of CBK” in a software switch
controller (SOTFSW). The IEC 61850 standard defines the “Command Blocking”
function as “CmdBlk”. For more information on CBK, see Chapter
Control and
monitoring application: Software switch controller. See the signal
S4301_STATE” of Table 4.2-7.
2
Note: “Double Command Blocking” (DCB) is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS. The DCB
operating signal is denoted as “DCB RCV OR) in Table 4.2-7.
3
Note: If the event “device-travelling” is detected, it indicates that another operator is
changing the status of a device. Thus, the IED should inhibit the operation of any
device for the duration that the event is detected. The detecting signal is denoted
as “Travelling OR” in Table 4.2-7.
4
Note: If the issue of a trip command is executed by the IED, any control operation is
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table
4.2-7.

Table of Contents

Related product manuals