- 713 -
Signal acquisition logic in DPSY01
“DPSY01_3PH_STATE”
(511001 3102011001)
To select and operate
condition logics
Event
Suppression
detector
BI signal selected by
setting [DPSY01A-NOPSG]
BI signal selected by
setting [DPSY01A-NCLSG]
BI signal selected by
setting [DPSY01B-NOPSG]
BI signal selected by
setting [DPSY01B-NCLSG]
BI signal selected by
setting [DPSY01C-NOPSG]
BI signal selected by
setting [DPSY01C-NCLSG]
“DPSY01_ F_QLT_SPP”
(511001 8102011F5F)
Figure 4.2-40 Acquisition of a state signal
†Note: The user should set the actual input-points. See chapter
Technical description:
Binary IO module
.
‡Note: In Figure 4.2-40 two signals can be issued: “DPSY01_3PH_STATE” and
“DPSY01_F_QLT_SPP”. One is used in the select condition logic and operate
condition logic (see Figure 4.2-13 and Figure 4.2-28). Another is used for operation
in the event suppression function. Other signals are also provided:
DPSY01_APH_STATE, DPSY01_BPH_STATE, and DPSY01_CPH_STATE.
Acquisition of a signal corresponding to a phase
Suppose that a state-signal is acquired on the two BI circuits at IO#1 slot. An individual phase
signal can be taken using the N/C and the N/O contacts; thus, the user should set two input-
points (8001001110 and 810101110 in 200B01†) for the settings [DPSY01A-NOPSG] and
[DPSY01A-NCLSG], respectively, as shown in Figure 4.2-41. The user should set the scheme
switch [DPSY01-DEVTYPE] to 1-Pole.