6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 719 -
Setting for the contact health check (normal setting, example)
Figure 4.2-49 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1 to BO4 contacts. To check that the contact health check function is working
correctly, the respective points of the BO-RBs should be connected as shown in Table 4.2-31, to
demonstrate that the settings are physically matched with the BO contacts.
Table 4.2-31 Setting example for contact health check
Example #1
Contact health check settings for example #1
“DPSY01_OSL_BO_FLG” is connected to “BO1” at IO#1
[DPSY01-OSLBORD] =” 200B018002001113”(BO1-RB)
OK
“DPSY01_FSL_BO_FLG” is connected to “BO2” at IO#1
[DPSY01-FSLBORD]=” 200B018102011113” (BO2-RB)
OK
“DPSY01_OEX_BO_CSF” is connected to “BO3” at IO#1
[DPSY01-OEXBORD]=” 200B018202021113” (BO3-RB)
OK
“DPSY01_FEX_BO_CSF” is connected to “BO4” at IO#1
[DPSY01-OEXBORD]=” 200B018302031113” (BO4-RB)
OK
Plus (+)
DPSY01_OSL_BO_FLG
(511001 8602011DC6)
SW1 is driven with
BO1 at IO#1
BO1
Drivers
Select-Closing
command
BO1-RB
(200B01_8002001113)
BO3
Operate-Closing
command
DPSY01_OEX_BO
(511001 8202011DD3)
BO4-RB
(200B01_8302031113)
BO4
Operate-Open
command
DPSY01_FEX_BO
(511001 8102011DD0)
BO3-RB
(200B01_8202021113)
SW2 is driven with
BO2 at IO#1
SW4 is driven with
BO4 at IO#1
Remote/Local-end
SW 3
SW 1
Minus ()
BIO module
43SW
Closing
BO2
Select-Open
command
DPSY01_FSL_BO_FLG
(511001 8A02011DC4)
BO2-RB
(200B01_8102011113)
SW 2
SW 4
Open
SW3 is driven with
BO3 at IO#1
Figure 4.2-49 Contact health check setting and 43SW diagram for example #1