- 733 -
◆ Connection point in PLC logic
DPSY(Function ID: 511001)
◆ Mapping points in DPSY01
DPSY(Function ID: 511001)
DPSY01 control command received. (Mapping Data)
Note: In the table above, the user will only find Element IDs and their names for the 1
st
device, but a 2
nd
and other devices are also provided in the DPSY function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “DPSY01_SC_OWS” point for
the 2
nd
device, use the description of “DPSY01_SC_OWS” in place of
“DPSY02_SC_OWS”. The user can obtain the ID value of
“DPSY02_SC_OWS” by using the following steps:
Step 1 Find the element ID for DPSY01_SC_OWS (i.e.,
“8002011D51”).
Step 2 Identify the number at the fifth digit from the ID. (i.e.,
“1”).
Step 3 Choose a new device number. (i.e. pick the number “2” for
the 2nd device).
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8002021D51” of
“DPSY02_SC_OWS”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.