6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 774 -
4.4.2 Cancel logic in SBO mode
In the SBO control mode the reception of the cancel command is possible when the cancel
conditions are satisfied. Accordingly, the function can discard the select command; finally, the
operation returns to the initial stage (i.e., Wait for a command.)
(i) Receiving “Cancel” from the remote-end
Figure 4.4-7 outlines the reception of the cancel command from the remote end.
Signal reception in
IEC61850
Cancel by the remote-end
Do nothing
Cancel
decision
Success
Failed
Cancel logic
Wait for a command
Operate logic
Operate command
Operate logic
Command Reset from the
remote-end
Select logic
Wait for a next command
Figure 4.4-7 Outline of cancel command from the remote-end
(ii) Input point required mapping
Figure 4.4-8 shows the cancel logic when a Cancel command (Remote-Cancel) signal enters
the OPTIM function. The input-point OPTR01_CONTROL_REQ” is the same point of the
Figure 4.4-5.
OPTIM function (Function ID: 529001)
OPTR01_CONTROL_REQ
Cancel command
Command Cancel
529001 700C016D08
510001 7001016D08
Input
Output
&
&
Successes to cancel
Operation Failed
Do nothing
To Wait for a command
Unmatched condition
detected
Cancel logic in OPTR
Figure 4.4-8 Cancel from the remote-end
Note: The criteria “unmatched conditions” are determined when “Test-bit status” in a
command is not identical to “IED test status”.