- 817 -
S43P logic programmed
by the user
SYNCHK01 and 02 functions
Figure 4.6-19 Bus-bar arrangement and PLC setting
Voltage selection should be considered in accordance with the arrangement of VTs.
Voltages V1 and V2 represent the running voltage (V
R
) and the incoming voltage (V
I
),
respectively. Consequently, V-L1 and V2-L1 are set for the scheme switches [SyncRy1-VR] and
[SyncRy1-VI], respectively. Table 4.6-8 shows the setting example for this arrangement.
Table 4.6-8 Setting example
Selection of running voltage
Either of V-L1 / V-L2 / V-L3
Selection of incoming voltage
Either of V2-L1 / V2-L2 / V2-L3
Selection of running voltage
Selection of incoming voltage