6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 817 -
&
V1
V2
DS1
DS2
CB1
DS1 closed
DS2 closed
Busbar#1
S43P logic programmed
by the user
Busbar#2
Selection of SYNCHK_Ry1
SYNC01_RY1_USE_STS
SYNCHK01 and 02 functions
Figure 4.6-19 Bus-bar arrangement and PLC setting
Voltage selection should be considered in accordance with the arrangement of VTs.
Voltages V1 and V2 represent the running voltage (V
R
) and the incoming voltage (V
I
),
respectively. Consequently, V-L1 and V2-L1 are set for the scheme switches [SyncRy1-VR] and
[SyncRy1-VI], respectively. Table 4.6-8 shows the setting example for this arrangement.
Table 4.6-8 Setting example
Setting Name
Description
Default
Setting item or value
SyncRy1-VR
Selection of running voltage
V-L1
Either of V-L1 / V-L2 / V-L3
SyncRy1-VI
Selection of incoming voltage
V2-L1
Either of V2-L1 / V2-L2 / V2-L3
SyncRy2-VR
Selection of running voltage
N.A
N.A
SyncRy2-VI
Selection of incoming voltage
N.A
N.A