6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 825 -
other IEDs and GOOSE, is necessary.
4.7.2 Interlock-check formula
Figure 4.7-2 shows a device (Q0) in the feeder bay, if a control action to operate (Q0) is required,
an interlock-check will be necessary. To control the device (Q0), the interlock-check must verify
the status of several devices in the busbar and the bay.
Q8
Q53
Q52
Q9
Q1
Q2
Q1B
Q0B
Q2B
Busbar1-A
Busbar2-A
Q0
Q15
Q25
Q69
F52VT
F27L
Figure 4.7-2 Example of device status and Interlock-check
In accordance with the arrangement of the devices shown in Figure 4.7-2, interlock-check
formulae can be configured from equations (4.7-1) to (4.7-9). The status of respective devices,
(stVal) and interlock operators (“•” and +) are placed on the right-hand side of the equations;
and the interlock condition (e.g. Q0(Closing)) is placed on the left-hand side of the equations.
The interlock operators are also shown in Table 4.7-2.






󰇛
     
󰇜
(4.7-1)






󰇛
     
󰇜
(4.7-2)





(4.7-3)

󰇛

󰇜


󰇡
󰇛



󰇜
󰇛
 
󰇜

󰇢

(4.7-4)

󰇛

󰇜


(4.7-5)

󰇛

 󰇛󰇜 
󰇜
(4.7-6)

󰇛



󰇜
(4.7-7)

󰇛



󰇜
(4.7-8)

(4.7-9)
where,