6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 833 -
Table 4.7-8 Signals generated in control functions
Control
function
Device status generated by the control
function described on the left column
stVal transposed in the node
SPOS
0(off)
0
1(on)
1
DPOS
0x40(Open)
0
0x40
0x80(Close)
1
0x80
device statusexcept 0x40 and 0x80
0
TPOS
0x01(P1)
1
0x02(P2)
2
0x04(P3)
4
device statusexcept 0x01, 0x02 and
0x04
0
BI
signal
0(off)
0
Note: Values are altered when AND, OR, or NOT is applied as an interlock
operator.
Note: Values are altered when COMP is applied as an interlock operator.
§Note: Values are altered when the DPOS output is an inverted signal.
4.7.4 Configuration of Interlock formulae
Interlock-check formulae should be stored in the Interlock database, as shown in Figure 4.7-1.
These formulae are configured using GR-TIEMS, and are uploaded into the ILK interlock
database.
Note: The configuration of interlock-check formulae is discussed separately. See chapter
Engineering tool: Interlock configurator
.