6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 846 -
(iii) Receiving “Select command On” from the local-end
Figure 4.8-5 outlines the reception of the Select command On from the local-end.
Signal reception
from the front panel
Select command On from the local-end
Signal output
Select
decision
Success
Failed
Select logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Off from the remote-end
Select command Off from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Select command On from the remote-end
Figure 4.8-5 Outline of Select command On
Input signal generated at the local-end
Figure 4.8-6 shows the Select logic when “Select command On (Local-ON-Control)” signal is
applied to the DPOS01 function. The signal is provided when an On key is pressed on the
IED front panel; the user is not required to take account of mapping. Note that the user should
set the scheme switch [DPOS01-CTRAHMI] to SBO when operation from the IED front panel
is required, we discuss how to set this in chapter
User interface: Control sub-menu
.
Output signal to BO
When the select condition signal is true, the DPOS01 function can issue a “Select success
signal at the output-point DPOS01_OSL_BO_CSF”.
Note: The DPOS01_OSL_BO_CSF” signal is the same as the signal shown in Figure
4.8-2. If the input signal Local-ON-Control” is not true, the DPOS01 function
returns to the Wait for a command stage.