- 64 -
Figure 2.6-7 exemplifies the IEEE C37.94 frame format; we should map the SCOM4-SA0
bit for sending the signal DIFGL.
Header
Ia3
Ib3
Ic3
COM5
CRC
Header
Ia2
Ib2
Ic2
I
0
CRC
Header
I
0
Ia
V
Ib
Ic
CRC
a. Sending frames for remote IEDs in IEEE C37.94
N=1
N=2
N=3
SCOM4-SA0_S
800211EBB0
b. Connections for sending using PLC function
8000001C23
DIFGL
COMM_ APPL function (Function ID: 4A9001)
DIFGL function
From DIFGL
SCOM
SCOM1
MS0
RA0
MS0
RA3
MS0
Spare
MS0
RA0
MS0
RA3
MS0
Spare
SCOM2
MS1
RA1
MS1
RA4
MS1
Spare
MS1
RA1
MS1
RA4
MS1
Spare
SCOM3
MS2
RA2
MS2
RA5
MS2
Spare
MS2
RA2
MS2
RA5
MS2
Spare
SCOM4
Local test
SA0
SA1
SA2
SA3
SA4
SA5
SA6
SA7
SA8
SA9
SA10
SA11
Figure 2.6-7 Mapping for sending signal using SCOM bit
Note: For more information, see
Chapter Relay application: Communication application
.
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].
Reception of DIFGL-operation signal from the remote
Figure 2.6-8 shows the TFC reception logic; PLC connection point R1.DIFGL_OP is used for
the signal receiving from the Remote-1_IED, another PLC connection point R2.DIFGL_OP
is used from the Remote-2_IED.