6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 860 -
4.8.2 Cancel logic for SBO mode
In the SBO control mode the reception of a cancel command is possible; when the cancel
conditions are satisfied, accordingly the function can discard the select command; finally, the
operation returns to the initial stage (i.e., “Wait for a command.)
(i) Receiving “Cancel” from the remote-end
Figure 4.8-14 depicts the cancel command procedure for a cancel command initiated from the
remote-end.
Signal reception in
IEC61850
Cancel from the remote-end
Do nothing
Cancel
decision
Success
Failed
Cancel logic
Wait for a command
Operate logic
Operate command
Operate logic
Select logics
Cancel from the local-end
Select command Off from the remote-end
Select command On from the remote-end
Select command Off from the local-end
Select command On from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Wait for a next command
Figure 4.8-14 Outline of ‘cancel command from the remote-end
Input point required mapping
Figure 4.8-15 depicts the cancel logic when a Cancel command (Remote-Cancel) signal is
applied to the DPOS01 function. The input-point “DEV01_CONTROL_REQ” is the same as
that for the signal Select command On (Remote-ON-Control).
Output signal to BO
The DPOS01 function can issue a Success to cancel signal at the monitoring point
DPOS01_CC_SS, when the DPOS01 function has determined that the signal Remote-cancel
is true. Another signal Operation failed is issued at monitoring point DPOS01_CC_FS if
the DPOS01 function is able to determine that the signal “Remote-cancel is not true.