6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 862 -
DPOS01 function (Function ID: 512001)
DPOS01_ CC_SS
(512001_8603011E95)
Cancel command
510001 7001016D08
Input
Output
Cancel logic in DPOS01
Cancel condition
&
&
Successes of cancel
Operation Failed
DPOS01_CC_FS
(512001_8703011E96)
Command Local-cancel
Do nothing
To Wait for a command
Figure 4.8-17 ‘Cancel’ from the front panel
Output signal to BO
The DPOS01 function, illustrated in Figure 4.8-17, is able to issue a “Success of cancel” signal
at the monitoring point DPOS01_CC_SS”, when the DPOS01 function determines that the
signal “Local-Cancel is true.
(iii) Cancel condition logic
Figure 4.8-18 shows the cancel condition logic. As the criteria, “Unmatched condition detected
is connected normally for the cancel logic, set Fixedlogic for the scheme switch [DPOS01-
LGCNFFCT].
DPOS01 function (Function ID: 512001)
User configurable condition (PLC connection point)
Fixedlogic
[DPOS01-LGCNFFCT]
To cancel logic in
DPOS01
Unmatched condition detected *1
DPOS01IN_TMP_44
512001 800301EE69
&
&
1
PLC#1
Figure 4.8-18 Logic “Cancel condition” in DPOS01
1
Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status” as in Figure 4.8-13.
2
Note: With the exception of the above cancel-condition logic, there is an operate-
condition logic within the DPOS01 function; the operate-condition logic will
always checks conditions. That is, the user is required to set either the operate-
condition” or the cancel-condition logic.
If the original logic does not meet with the requirement of the user, it can be relpced using
the connection point “User configurable condition”.
1. Connect the user-customized logic with the “DPOS01IN_TMP_44”, which is listed
in Table 4.8-11.
2. Set scheme switch [DPOS01-LGCNFFCT] to PLC.