6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 892 -
Setting for “Select command On
For example, the point DPOS01_OSL_BO_FLG is connected to the BO1 circuit for the issuing
of the command; the user can connect point BO1-RB with the contact health check function
using the setting [DPOS01-OSLBORD]. Do not key the point “DPOS01_OSL_BO_FLG .
DPOS01_OSL_BO_FLG
(512001 8603011DC6)
Selecte logic in
DPOS01
&
Signal connected by
setting [DPOS01-OSLBORD]
BO1-RB
(200B01_8002001113)
BO1 circuit at
IO#1
Contact health check
logic in DPOS01
Result of contact health check
Connection made by the user
Figure 4.8-45 Example connection of “Select command On” for the health check feature
Setting for “Select command Off”
Similar to select command On, the point DPOS01_FSL_BO_FLG is connected with the BO2
circuit; the user is required to key point BO2-RB for the setting [DPOS01-FSLBORD]. Do not
key the point DPOS01_FSL_BO_FLG.
DPOS01_FSL_BO_FLG
(55120018 A03011DC4)
Selection logic in
DPOS01
&
Signal connected by
setting [DPOS01-FSLBORD]
BO2-RB
(200B01_8102001113)
BO1 circuit at
IO#1
Contact health check
logic in DPOS01
Result of contact health check
Connection made by the user
Figure 4.8-46 Example connection of “Select command Off” for the health check feature