- 892 -
Setting for “Select command On”
For example, the point “DPOS01_OSL_BO_FLG” is connected to the BO1 circuit for the issuing
of the command; the user can connect point “BO1-RB” with the contact health check function
using the setting [DPOS01-OSLBORD]. Do not key the point “DPOS01_OSL_BO_FLG” .
“DPOS01_OSL_BO_FLG”
(512001 8603011DC6)
Signal connected by
setting [DPOS01-OSLBORD]
“BO1-RB”
(200B01_8002001113)
Contact health check
logic in DPOS01
Result of contact health check
Connection made by the user
Figure 4.8-45 Example connection of “Select command On” for the health check feature
Setting for “Select command Off”
Similar to “select command On”, the point “DPOS01_FSL_BO_FLG” is connected with the BO2
circuit; the user is required to key point “BO2-RB” for the setting [DPOS01-FSLBORD]. Do not
key the point “DPOS01_FSL_BO_FLG”.
“DPOS01_FSL_BO_FLG”
(55120018 A03011DC4)
Selection logic in
DPOS01
Signal connected by
setting [DPOS01-FSLBORD]
“BO2-RB”
(200B01_8102001113)
Contact health check
logic in DPOS01
Result of contact health check
Connection made by the user
Figure 4.8-46 Example connection of “Select command Off” for the health check feature