6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 895 -
Settings for erroneous contact health check (improper setting, example #2)
Figure 4.8-50 shows a setting example of an improper setting of the 43SW scheme. The settings
are implemented incorrectly as shown in Table 4.8-30, BO1-RB is not chosen, instead BO1 is
actually chosen, which is incorrect. In this case, the setting [DPOS01-OSLBORD] is
meaningless ; hence, the issue of a select command is blocked.
Table 4.8-30 Erroneous setting example for contact health check
Example #2
Contact health check setting for example #2
DPOS01_OSL_BO_FLG is connected to BO1 at IO#1
200B01 8002001112 (BO1) set for [DPOS01-OSLORD]
NG
DPOS01_FSL_BO_FLG is connected to BO2 at IO#1
200B01 8102011113 (BO2-RB) set for [DPOS01-FSLBORD]
OK
DPOS01_OEX_BO_CSF” is connected to BO3 at IO#1
200B01 8202021113(BO3-RB) set for [DPOS01-OEXBORD]
OK
DPOS01_FEX_BO_CSF” is connected to BO4 at IO#1
200B01 8302031113(BO4-RB) set for [DPOS01-FEXBORD]
OK
Plus (+)
DPOS01_OSL_BO_FLG
(512001 8603011DC6)
SW1 is driven with
BO1 at IO#1
BO1
Drivers
BO3
DPOS01_OEX_BO
(512001 8203011DD3)
BO4-RB
(200B01_8302031113)
BO4
DPOS01_FEX_BO
(512001 8103011DD0)
BO3-RB
(200B01_8202021113)
SW2 is driven with
BO2 at IO#1
SW4 is driven with
BO4 at IO#1
Local/Remote-end
SW 3
SW 1
Minus ()
BIO module
43SW
BO2
DPOS01_FSL_BO_FLG
(512001 8A03011DC4)
BO2-RB
(200B01_8102011113)
SW 2
SW 4
SW3 is driven with
BO3 at IO#1
BO1 (not BO1-RB)
mistakenly chosen with
200B01_8002001112
Select command On
On
command
Select command Off
Operate command On
Operate command Off
Off
command
Figure 4.8-50 Contact health check setting and 43SW scheme for example#2