Toshiba GR200 Series - (iv)-7 Settings for extra contact health check (special setting, example #3)

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 896 -
Settings for extra contact health check (special setting, example #3)
Figure 4.8-51 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point DPOS01_OSL_BO_FLG is actually chosen for the
setting [DPOS01-OSLBORD]; i.e. BO1-RB is not chosen for this selection. This special setting
can issue a select command, which is called operated by internal select function. The user
does not need to consider the use of a BO circuit for a select command, when there are no BIO
circuits available.
Table 4.8-31 Extra setting example for contact health check
Example #3
Contact health check setting for example #3
DPOS01_OSL_BO_FLG is not connected to any BO
DPOS01_OSL_BO_FLG set for [DPOS01-OSLBORD]
OK
DPOS01_FSL_BO_FLG is not connected to any BO
DPOS01_OSL_BO_FLG set for [DPOS01-FSLBORD]
OK
DPOS01_OEX_BO_CSF” is connected to BO3 at IO#1
200B01 8102011113(BO2-RB) set for [DPOS01-OEXBORD]
OK
DPOS01_FEX_BO_CSF” is connected to BO4 at IO#1
200B01 8202021113 (BO3-RB) set for [DPOS01-FEXBORD]
OK
Plus (+)
DPOS01_OSL_BO_FLG
(512001 8603011DC6)
Drivers
BO3
DPOS01_OEX_BO
(512001 8203011DD3)
BO4-RB
(200B01_8302031113)
BO4
DPOS01_FEX_BO
(512001 8103011DD0)
BO3-RB
(200B01_8202021113)
SW4 is driven with
BO4 at IO#1
Remote/Local-end
SW 3
SW 1
Minus ()
BIO module
43SW
DPOS01_FSL_BO_FLG
(512001 8A03011DC4)
SW 2
SW 4
SW3 is driven with
BO3 at IO#1
SW1 is not driven with any BO
SW2 is not driven with any BO
Physical BOs
are virtualized.
Select command On
Select command Off
Operate command On
Operate command Off
On
command
Off
command
Figure 4.8-51 Contact health check setting and 43SW scheme for example#3