Toshiba GR200 Series - (vii)-1 Input signal from the PLC function

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 919 -
PLC logic programmed
by the user
P1control by the PLC function
Signal output
Select
decision
Success
Failed
Selection logic
P2 control from the remote-end
P3 control from the remote-end
P1 control from the local-end
P2 control from the local-end
P2 control by the PLC function
P3 control from the local-end
P3 control by the PLC function
Select stage
Cancel logic
Wait for a command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
P1 control from the remote-end
Figure 4.9-14 Outline of select command P1-control’
Input signal from the PLC function
Figure 4.9-15 shows the select logic when a “Select command P1-Control (PLC-P1-Control)”
signal is generated by the PLC function. There are two input points for the reception: the
former connection point(PLC#1) is used for the reception of the select-command when the
interlock check is required, the later connection point(PLC#2) is used for the reception of the
select-command when the interlock check is not required. That is, for the TPOS01 function,
when the signal “Select command P1-Contol (PLC-P1-Control)” generated in the user-
programmed logic is applied for the select logic, and when interlock-check is required in the
select-logic, use connection point (PLC#1:e.g.,DEV01_P1_INTERLOCK)”. Alternatively, if the
interlock check is not required, use the other connection point (PLC#2:e.g.,
DEV01_P1_COMMAND)”. PLC#1 and PLC#2 are shown in Table 4.9-2.