Toshiba GR200 Series - (viii)-1 Input signal from the PLC function

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 921 -
PLC logic programmed
by the user
P2control by the PLC function
Signal output
Select
decision
Success
Failed
Selection logic
P2 control from the remote-end
P3 control from the remote-end
P1 control from the local-end
P2 control from the local-end
P1 control by the PLC function
P3 control from the local-end
P3 control by the PLC function
Select stage
Cancel logic
Wait for a command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
P1 control from the remote-end
Figure 4.9-16 Outline of select command P2-control’
Input signal from the PLC function
Figure 4.9-17 shows the select logic when a signal “Selection command P2-Control (PLC-P2-
Control)” is generated by the PLC function. There are two input points for the reception, like
in the “Select command P1-Control (PLC-P1-Control)” signal. That is, if interlock checking is
required, use connection point (PLC#1:e.g., DEV01_P2_INTERLOCK). Alternatively, if the
inter-lock check is not required, use the connection point (PLC#2:e.g., DEV01_P2_COMMAND).
PLC#1 and the PLC#2 are shown in Table 4.9-3.