- 924 -
TPOS01 function (Function ID: 513001)
Operate command
without ILK† condition
ILK† condition (“P3”) passed
Signals from user-PLC logic
Selection logic in TPOS01
P3-control command requiring with ILK† check
(PLC connection point #1)
P3-control command not requiring without ILK† check
(PLC connection point #2)
Operate command
with ILK† condition
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
Figure 4.9-19 Select ‘P3-control’ using the PLC function in TPOS01
††
††
Note: To know the input and output points of the other TPOS logics, see Table 4.9-4 for
the input PLC#1 and PLC#2 and Table 4.9-10 for the outputs.
Output signal to BO
The TPOS01 function, in Figure 4.9-19, can issue a “Select success” signal at the output point
“TPOS01_P3SL_BO_FLG”
1
.
1
Note: The output point “TPOS01_P3SL_BO_FLG” is the same as the signal shown in
Figure 4.9-7.
(x) Select condition
Figure 4.9-20 shows the select condition logic in the TPOS01 function. The TPOS01 function
can check the condition for the select command using the signals “TPOS01_ST_P1”,
“TPOS01_ST_P2”, and “TPOS01_ST_P3” (see Table 4.9-35). If the original logic does not meet
with the requirements of the user, the following alternatives are available:
1. The user can replace the original logic with alternative logic,
2. The user can add additional logic to the original logic.
How to replace the original logic
If the user wishes to replace the select condition logic, the user can replace it using the PLC
connection point “User configurable condition” set items:
1. Connect the user-customized logic with TPOS01IN_TMP_25, which is listed as PLC#2
in Table 4.9-8.
2. Set the scheme switch [TPOS01-LGSLFFCT] to PLC.