6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 924 -
TPOS01 function (Function ID: 513001)
DEV01_P3_INTERLOCK
Operate command
without ILK condition
ILK condition (“P3”) passed
PLC in DIR operate
513001 800401EE37
510001 7001016D08
TPOS1-P3
Signals from user-PLC logic
Output
Selection logic in TPOS01
0.1s
0
t
0.6s
0
t
&
&
&
Select condition
1
P3-control command requiring with ILK† check
(PLC connection point #1)
DEV01_P3_COMMAND
513001 800401EE36
P3-control command not requiring without ILK† check
(PLC connection point #2)
Operate command
with ILK condition
For DIR operation
For DIR operation
TPOS01_P3SL_BO_FLG
(513001 8A04011DC8)
Select Failed
To BO connection
Select success
To Wait for a command
Figure 4.9-19 Select ‘P3-control’ using the PLC function in TPOS01
††
††
Note: To know the input and output points of the other TPOS logics, see Table 4.9-4 for
the input PLC#1 and PLC#2 and Table 4.9-10 for the outputs.
Output signal to BO
The TPOS01 function, in Figure 4.9-19, can issue a “Select success” signal at the output point
“TPOS01_P3SL_BO_FLG
1
.
1
Note: The output point “TPOS01_P3SL_BO_FLG is the same as the signal shown in
Figure 4.9-7.
(x) Select condition
Figure 4.9-20 shows the select condition logic in the TPOS01 function. The TPOS01 function
can check the condition for the select command using the signals TPOS01_ST_P1,
TPOS01_ST_P2, and TPOS01_ST_P3 (see Table 4.9-35). If the original logic does not meet
with the requirements of the user, the following alternatives are available:
1. The user can replace the original logic with alternative logic,
2. The user can add additional logic to the original logic.
How to replace the original logic
If the user wishes to replace the select condition logic, the user can replace it using the PLC
connection point “User configurable condition” set items:
1. Connect the user-customized logic with TPOS01IN_TMP_25, which is listed as PLC#2
in Table 4.9-8.
2. Set the scheme switch [TPOS01-LGSLFFCT] to PLC.