6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 947 -
apply the signal at other connection point (PLC#4; i.e., DEV01_P1_COMMAND). We should
assume the PLC#3 and PLC#4 as PLC#1 and PLC#2 in Table 4.9-2. Note that the user should
set PLC for scheme switch [TPOS01-LGP1EXOT].
TPOS01 function (Function ID: 513001)
Assign to BOs
Operate Cmd.
with ILK condition
S
R
0.1 50.0 s
[TPOS01-CPW]
Operate Cmd.
without ILK condition
Operate condition
[TPOS01-LGCTRCON]
Fixedlogic
Fixedlogic
[TPOS01-LGP1EXOT]
Command PLC-P1-Control requiring ILK check
(PLC#3 connection point)
ILK condition (“P1”) passed
TPOS1-P1
TPOS01IN_TMP_27
513001 800401EE56
User configurable condition
(PLC#1 connection point)
TPOS01_P1EC_OK_CSF
(513001 8004011E7E)
&
&
1
&
1
1
&
&
&
TPOS01_P1EX_BO
(5130018104011DD0) §§
Input
Output
Operate logic in TPOS01
To BO connection
TPOS01_P1EC_OK_CS
(5130018004011E81)
[TPOS01-PLSM]*
Fix
Var
Operate Failed
[TPOS01-RST]
ASEQ function§ is in progress
ASEQ_MULTI_SEL
TPOS01_P1EC_OK_CSF
(513001 8004011E7E)
TPOS01_EX_FFL
(513001 8604011E91) ‡‡
To Wait for a command
&
Detection of state-change in a device
&
TPOS01IN_TMP_38
513001 820401EE5E
User configurable condition
(PLC#2 connection point)
1
&
TPOS01_EX_CMP
(5130018004011E93)
Operate Completed
1.0s- 100.0s
0
t
DEV01_P1_INTERLOCK
513001 800401EE31
Command PLC-P1-Control not requiring ILK check
(PLC#4 connection point)
DEV01_P1_COMMAND
513001 800401EE30
Figure 4.9-39 Operate P1- control using the PLC function in TPOS01
††
Note: The ILK function can provide the criteria for operation for P1” control.
Note: An operate condition signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
“operate-condition” to the logic shown in Figure 4.9-39 using connection point #1
“User configurable condition” That is, set the scheme switch [TPOS01-
LGCTRCON] to PLC and use “TPOS01IN_TMP_27”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting applied
to [TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
††
Note: To identify the input and output signal-points of the P1-control in the other TPOS
logics, see Table 4.9-15 for PLC#1, Table 4.9-16 for PLC#2 and Table 4.9-20 for the
outputs.