- 962 -
4.9.5 Measurement of operation Intervals
The TPOS01 function can measure operation intervals time†, the intervals OT1 and OT2 can
represent the period of time when an earth-switch changes a position from another position.
As shown in Table 4.9-27 the eight intervals are defined as switching as shown in Figure 4.9-50
to Figure 4.9-53. The user should set scheme switch [TPOS01-OPETMEN] On.
Sensing intermediate state
a. Switch motion (P1 to P2)
b. Operate command and signals with regard to the switch motion (P1 to P2)
Figure 4.9-50 Two Intervals (OT1 and OT2) for P2 control
Sensing intermediate state
a. Switch motion (P2 to P1)
b. Operate command and signals with regard to the switch motion (P2 to P1)
Figure 4.9-51 Two Intervals (OT3 and OT4) for P1 control
Sensing Intermediate state
a. Switch motion (P3 to P2)
b. Operate command and signals with regard to the switch motion (P3 to P2)
Figure 4.9-52 Two Intervals (OP5 and OP6) for P2 control