4.9.5 Measurement of operation Intervals
The TPOS01 function can measure operation intervals time†, the intervals OT1 and OT2 can
represent the period of time when an earth-switch changes a position from another position.
As shown in Table 4.9-27 the eight intervals are defined as switching as shown in Figure 4.9-50
to Figure 4.9-53. The user should set scheme switch [TPOS01-OPETMEN] On.
Signal TPOS01_PT_P1
Signal TPOS01_PT_P2
Signal TPOS01_PT_P3
Signal TPOS01_P2EX_BO
OT1
OT2
Sensing intermediate state
P1
P2-control
P2
Intermediate
a. Switch motion (P1 to P2)
b. Operate command and signals with regard to the switch motion (P1 to P2)
Intermediate
P3
Figure 4.9-50 Two Intervals (OT1 and OT2) for P2 control
Signal TPOS01_PT_P1
Signal TPOS01_PT_P2
Signal TPOS01_PT_P3
Signal TPOS01_P1EX_BO
OT3
OT4
Sensing intermediate state
P1
P1-control
P2
Intermediate
a. Switch motion (P2 to P1)
b. Operate command and signals with regard to the switch motion (P2 to P1)
Intermediate
P3
Figure 4.9-51 Two Intervals (OT3 and OT4) for P1 control
Signal TPOS01_PT_P1
Signal TPOS01_PT_P2
Signal TPOS01_PT_P3
Signal TPOS01_P2EX_BO
OT5
OT6
Sensing Intermediate state
P3
P2-control
P2
Intermediate
a. Switch motion (P3 to P2)
b. Operate command and signals with regard to the switch motion (P3 to P2)
Intermediate
P1
Figure 4.9-52 Two Intervals (OP5 and OP6) for P2 control