Proper setting for the contact health check (normal setting, example #1)
Figure 4.9-61 shows a setting example for 43S/EDS driving. Select and operate commands
drive the BO1BO6 contacts. To check that the contact health check function is working
correctly, the respective points of the BO (RBs) should be connected, as shown in Table 4.9-31,
to demonstrate that the settings are physically matched with the BO contacts.
Table 4.9-31 Setting example for contact health check
Example #1
Health check settings for example #1
TPOS01_P1SL_BO_FLG is connected to BO1 at IO#1
200B01 8002001113(BO1-RB) set for [TPOS01-P1SLBORD]
OK
TPOS01_P2SL_BO_FLG is connected to BO2 at IO#1
200B01 8102011113(BO2-RB) set for [TPOS01-P2SLBORD]
OK
TPOS01_P3SL_BO_FLG is connected to BO3 at IO#1
200B01 8202021113(BO3-RB) set for [TPOS01-P3SLBORD]
OK
TPOS01_P1EX_BO” is connected to BO4 at IO#1
200B01 8302031113(BO4-RB) set for [TPOS01-P1EXBORD]
OK
TPOS01_P2EX_BO” is connected to BO5 at IO#1
200B01 8402041113(BO5-RB) set for [TPOS01-P2EXBORD]
OK
TPOS01_P3EX_BO” is connected to BO6 at IO#1
200B01 8502051113(BO6-RB) set for [TPOS01-P3EXBORD]
OK