- 973 -
Table 4.9-32 Erroneous setting example for contact health check
Health check setting for example #2
“TPOS01_P1SL_BO_FLG” is connected to “BO1” on SLOT1
200B01 8002001112 (BO1) set for [TPOS01-P1SLBORD]
“TPOS01_P2SL_BO_FLG” is connected to “BO2” on SLOT1
200B01 8102011113(BO2-RB) set for [TPOS01-P2SLBORD]
“TPOS01_P3SL_BO_FLG” is connected to “BO3” on SLOT1
200B01 8202021113(BO3-RB) set for [TPOS01-P3SLBORD]
“TPOS01_P1EX_BO” is connected to “BO4” on SLOT1
200B01 8302031113(BO4-RB) set for [TPOS01-P1EXBORD]
“TPOS01_P2EX_BO” is connected to “BO5” on SLOT1
200B01 8402041113(BO5-RB) set for [TPOS01-P2EXBORD]
“TPOS01_P3EX_BO” is connected to “BO6” on SLOT1
200B01 8502051113(BO6-RB) set for [TPOS01-P3EXBORD]
“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
P1
driven
with
BO1
and
BO4
“TPOS01_P1EX_BO”
(513001 8104011DD0)
“BO4-RB”
(200B01 8302031113)
“TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
“BO2-RB”
(200B01 8102011113)
“TPOS01_P2EX_BO”
(513001 8204011DD3)
“BO5-RB”
(200B01 8402041113)
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
“BO3-RB”
(200B01 8202021113)
“TPOS01_P3EX_BO”
(513001 8204031DD3)
“BO6-RB”
(200B01 8502051113)
“BO1” (not BO1-RB)
mistakenly chosen with
200B01 8002001112
Figure 4.9-62 Contact health check setting and EDS diagram for example #2
Setting for extra contact health check (special setting, example #3)
Figure 4.9-63 shows an additional setting example for the EDS scheme; one of the settings is
made hypothetically. That is, the point “SPO01_P1*SL_BO_FLG” is actually chosen for the
setting [TPOS01-P1*SLBORD]; i.e. BO1-RB is not chosen for this selection. This special