How to fix communication trouble on Toshiba GRL150-100 Relays (IEC103)?
- JJason MccormickAug 3, 2025
If your Toshiba Relays experience communication trouble with IEC103, begin by verifying the address settings between the BCU and the relay, ensuring there are no address duplications. Then, confirm that the transmission baud rate settings are identical between the BCU and the relay. Also, check the start bit, stop bit, and parity settings of the data transmitted by the BCU to the relay, ensuring they match the relay's fixed settings: 1 start bit, 1 stop bit, and even parity. If the issue persists, check the connection port (CH1/CH2), the RS485 A/B/COM interconnection, and the send/receive interconnection of the optical cable. If using RS485, ensure a terminal resistor (150 ohms) is correctly placed at both ends of the RS485 cable.