96 H7 ASD Operation Manual
RX2 Torque Reference Setpoint #2 (%)
Program
Torque Setting Parameters
Setpoints
RX2
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given RX2 input level and motor load.
See F222 for further information on this setting.
This parameter sets RX2 Torque Reference Setpoint #2 (%) and is the output
torque value that is associated with the setting of F224. This value is entered as
-250 to +250% of the rated torque.
Direct Access Number F227
Parameter TypeNumerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
F227 F227