H7 ASD Operation Manual 109
PWM Carrier Frequency
Program
Special Control Parameters
Carrier Frequency
This parameter sets the frequency of the pulse width modulation signal applied
to the output waveform.
Note: For proper operation, the carrier frequency must be 2.2 kHz or above
except when operating in the Constant Torque, Variable Torque, or the
5-Point Setting modes.
Direct Access Number F300
Parameter TypeNumerical
Factory Default2.200
Changeable During Run — No
Minimum — 0.500
Maximum — 15.000
Units — kHz
Break/Make ST
Program
Protection Parameters
Retry/Restart
This parameter Enables/Disables the ability of the drive to start into a spinning
motor when the STCC connection momentarily opens and is then closed
(Break/Make ST) or after a power interruption (momentary power failure). This
parameter also Enables/Disables F312 and F313.
Direct Access Number F301
Parameter TypeCheck Box
Factory DefaultDisabled
Changeable During Run — Yes
Ridethrough Mode
Program
Protection Parameters
Undervoltage/Ridethrough
This parameter determines the motor-control response of the drive in the event
of a momentary power outage.
Settings:
Off
Ridethrough
Stop
Direct Access Number F302
Parameter TypeSelection List
Factory DefaultOff
Changeable During Run — Yes
Number of Retries
Program
Protection Parameters
Retry/Restart
After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted.
See the section titled Safety Precautions on pg. 2 for further information on this
setting.
Direct Access Number F303
Parameter TypeNumerical
Factory Default00
Changeable During Run — Yes
Minimum — 00
Maximum — 10
F300 F303