114 H7 ASD Operation Manual
Drooping Output Filter
Program
Feedback Parameters
Drooping Control
Contact Toshiba’s Marketing Department for information on this parameter.
Direct Access Number F324
Parameter TypeNumerical
Factory Default100.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 200.0
Load Inertia (Acc/Dec Torque)
Program
Feedback Parameters
Drooping Control
Load Inertia
This parameter is used for calculating accel/decel torque when compensating
for load inertia while operating in the Drooping Control mode.
Direct Access Number F325
Parameter TypeNumerical
Factory Default1.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 1000.0
Load Torque Filter (Acc/Dec Torque)
Program
Feedback Parameters
Drooping Control
Load Inertia
This parameter is used to set the response sensitivity when calculating the accel/
decel torque. This setting applies to load inertia compensation while operating
in the Drooping Control mode.
This parameter should be gradually adjusted to provide smoother Drooping
Control operation while operating with heavy loads.
Direct Access Number F326
Parameter TypeNumerical
Factory Default200.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 200.0
Drooping Reference
Program
Feedback Parameters
Drooping Control
Drooping
Reference
This parameter sets the method to be used in determining the output torque
while operating in the Drooping Control mode.
Settings:
Total Torque Calculated by the Detection Current.
Torque without Acc/Dec Torque Calculated by Detection Current.
Total Torque Calculated by the Command Current.
Torque without Acc/Dec Torque Calculated by the Command Current.
Direct Access Number F327
Parameter TypeSelection List
Factory DefaultTotal torque
calculated by the detection current
Changeable During Run — Yes
On-Trip Powerline Switching
Program
Terminal Selection Parameters
Line Power Switching
This parameter Enables/Disables the On Trip Powerline Switching feature.
When enabled, the system is instructed to discontinue using the output of the
drive and to switch to the commercial power in the event of a trip.
Direct Access Number F354
Parameter TypeCheck Box
Factory DefaultDisabled
Changeable During Run — No
F324 F354