118 H7 ASD Operation Manual
PG Input Phases
Program
Feedback Parameters
PG Settings
This parameter determines the type of information that is supplied by the phase
encoder.
Settings:
1 — Speed
2 — Speed and Direction
Direct Access Number F368
Parameter TypeSelection List
Factory Default2
Changeable During Run — No
Minimum — 1
Maximum2
Units — Phase Count
PG Disconnect Detection
Program
Feedback Parameters
PG Settings
This parameter Enables/Disables the system’s monitoring of the PG connection
status when using encoders with line driver outputs.
Direct Access Number F369
Parameter TypeSelection List
Factory DefaultDisabled
Changeable During Run — No
Electronic Gear Setting
Program
Feedback Parameters
PG Settings
This parameter sets the number of pulses per revolution when using a shaft-
mounted encoder and the PG Option Board for closed loop speed control.
Direct Access Number F370
Parameter TypeNumerical
Factory Default1000
Changeable During Run — No
Minimum — 100
Maximum — 4000
Position Loop Gain
Program
Feedback Parameters
PG Settings
This parameter provides a divisor for the pulse input when operating in the
Pulse Control mode.
Direct Access Number F371
Parameter TypeNumerical
Factory Default4.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
F368 F371