122 H7 ASD Operation Manual
Preset Speed Direction #11
Program
Pattern Run Control Parameters
Preset Speeds
Determines the forward/reverse setting for the #11 Preset Speed (F290).
Direct Access Number F391
Parameter Type Selection List
Factory Default Forward
Changeable During Run — No
Preset Speed Direction #12
Program
Pattern Run Control Parameters
Preset Speeds
Determines the forward/reverse setting for the #12 Preset Speed (F291).
Direct Access Number F392
Parameter Type Selection List
Factory Default Forward
Changeable During Run — No
Preset Speed Direction #13
Program
Pattern Run Control Parameters
Preset Speeds
Determines the forward/reverse setting for the #13 Preset Speed (F292).
Direct Access Number F393
Parameter Type Selection List
Factory Default Forward
Changeable During Run — No
Preset Speed Direction #14
Program
Pattern Run Control Parameters
Preset Speeds
Determines the forward/reverse setting for the #14 Preset Speed (F293).
Direct Access Number F394
Parameter Type Selection List
Factory Default Forward
Changeable During Run — No
Preset Speed Direction #15
Program
Pattern Run Control Parameters
Preset Speeds
Determines the forward/reverse setting for the #15 Preset Speed (F294).
Direct Access Number F395
Parameter Type Selection List
Factory Default Forward
Changeable During Run — No
Vector Motor Model Autotune Command
Program
Motor Parameters
Vector Motor Model
This parameter sets the Autotune command status.
Settings:
Autotune Disabled
Reset Motor Defaults
Enable Autotune on Run Command
Direct Access Number F400
Parameter Type Selection List
Factory Default Autotune Disabled
Changeable During Run — No
Vector Motor Model Slip Frequency Gain
Program
Motor Parameters
Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
Direct Access Number F401
Parameter Type Numerical
Factory Default 0.60
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 2.55
F391 F401
www . ElectricalPartManuals . com