H7 ASD Operation Manual 125
Torque Command Filter
Program
Torque Setting Parameters
Torque Control
This parameter reduces the motor vibration caused by large-inertia loads. A
small value will have a great effect while an increased value will have a lesser
effect.
Direct Access Number F421
Parameter Type Numerical
Factory Default 200.0
Changeable During Run — Ye s
Minimum — 10.0
Maximum — 200.0
Synchronized Torque Bias Input
Program
Torque Setting Parameters
Torque Control
This parameter Enables/Disables the Synchronized Torque Bias input
function. When enabled, this parameter identifies the source of the
Synchronized Torque Bias input signal.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
LED Keypad Option
Binary/BCD Input
Common Serial (TTL)
RS232/485
Communication Card
Direct Access Number F422
Parameter Type Selection list
Factory Default Disabled
Changeable During Run — Ye s
Tension Torque Bias Input
Program
Torque Setting Parameters
Torque Control
This parameter Enables/Disables the Tension Torque Bias input function and
identifies the source of the Tension Torque Bias input signal when enabled.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
LED Keypad Option
Binary/BCD Input
Common Serial (TTL)
RS232/485
Communication Card
Direct Access Number F423
Parameter Type Selection List
Factory Default Disabled
Changeable During Run — Ye s
F421 F423