H7 ASD Operation Manual 135
Current Vector Control
Program
Special Control Parameters
Special Parameters
Control Margin Modulation
% Current Vector Control
This parameter establishes the control margin of modulation when operating in
the Current Vector Control mode.
Direct Access Number F482
Parameter Type Numerical
Factory Default 90.0
Changeable During Run — Ye s
Minimum — 80.0
Maximum — 300.0
Units — %
Voltage Vector Control
Program
Special Control Parameters
Special Parameters
Control Margin Modulation
% Voltage Vector Control
This parameter establishes the control margin of modulation when operating in
the Voltage Vector Control mode.
Direct Access Number F483
Parameter Type Numerical
Factory Default 105.0
Changeable During Run — Ye s
Minimum — 80.0
Maximum — 300.0
Units — %
Constant Vector Control
Program
Special Control Parameters
Special Parameters
Control Margin Modulation
% Voltage Vector Control
This parameter establishes the control margin of modulation when operating in
the Constant Vector Control mode.
Direct Access Number F484
Parameter Type Numerical
Factory Default 105.0
Changeable During Run — Ye s
Minimum — 80.0
Maximum — 300.0
Units — %
Compensation Coefficient for Iron Loss
Program
Special Control Parameters
Special Parameters
Compensation Coefficient for Iron Loss
This parameter compensates for losses in the rotor-to-stator coupling of the
excitation and torque current energy.
Direct Access Number F487
Parameter Type Numerical
Factory Default 105.0
Changeable During Run — Ye s
Minimum — 0
Maximum — 255
F482 F487