140 H7 ASD Operation Manual
S-Pattern Upper Limit Adjustment
Program
Special Control Parameters
Accel/Decel Special
Sets the upper limit frequency of S-pattern 1 and 2.
Direct Access Number F507
Parameter TypeNumerical
Factory Default25.00
Changeable During Run — Yes
Minimum — 0.00
Maximum50.00
Units — %
Accel/Decel Lower Limit Time
Program
Special Control Parameters
Accel/Decel Special
This parameter sets the lower limit of the Accel/Decel time.
Direct Access Number F508
Parameter TypeNumerical
Factory Default0.10
Changeable During Run — Yes
Minimum — 0.01
Maximum10.00
Units — Seconds
Accel #3 Time
Program
Special Control Parameters
Accel/Decel #1 – #4
Settings
This parameter specifies the time in seconds for the drive to go from 0.0 Hz to
the Maximum Frequency for the #3 Acceleration profile. The accel/decel
pattern may be set using F502. The minimum accel/decel time may be set using
F508.
Note: An acceleration time shorter than the load will allow may cause nuisance
tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the acceleration
time.
Direct Access Number F510
Parameter TypeNumerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Decel #3 Time
Program
Special Control Parameters
Accel/Decel #1 – #4
Settings
This parameter specifies the time in seconds for the drive to go from the
Maximum Frequency to 0.0 Hz for the #3 Deceleration profile.
The accel/decel pattern may be set using F502. The minimum accel/decel time
may be set using F508.
Note: A deceleration time shorter than the load will allow may cause nuisance
tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the deceleration
time.
Direct Access Number F511
Parameter TypeNumerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
F507 F511