156 H7 ASD Operation Manual
OL Reduction Starting Frequency
Program
Protection Parameters
Overload
This parameter is used to reduce the start frequency during very low-speed
motor operation. During very low-speed operation the cooling efficiency of the
motor decreases. Lowering the start frequency aides in minimizing the
generated heat.
Direct Access Number F606
Parameter TypeNumerical
Factory Default6.00
Changeable During Run — Yes
Minimum — 0.00
Maximum30.00
Units — Hz
Motor 150% OL Time Limit
Program
Protection Parameters
Overload
This parameter establishes a time that the motor may operate at 150% of its
rated current before tripping. This setting applies the time/150% reference to
the individual settings of each motor (e.g., this setting references 150% of the
F600 setting for the #1 motor).
The unit will trip sooner than the time entered here if the overload is greater
than 150%.
Direct Access Number F607
Parameter TypeNumerical
Factory Default600
Changeable During Run — Yes
Minimum — 10
Maximum — 2400
Units — Seconds
Inrush Current Suppression
Program
Protection Parameters
Soft Start
The startup inrush current may be suppressed for up to 2.5 seconds. This
parameter determines the length of the inrush current suppression.
Direct Access Number F608
Parameter TypeNumerical
Factory Default0.30
Changeable During Run — No
Minimum — 0.30
Maximum — 2.50
Units — Seconds
Interlock with ST
Program
Protection Parameters
Soft Start
This parameter Enables/Disables the ST-to-CC connection dependency on the
successful completion of a Soft Start. If enabled, the ST-to-CC connection will
happen only after a successful Soft Start.
Direct Access Number F609
Parameter TypeCheck Box
Factory DefaultDisabled
Changeable During Run — No
Low Current Trip
Program
Protection Parameters
Low Current Settings
This parameter Enables/Disables the low-current trip feature.
When enabled, the drive will trip on a low-current fault if the output current of
the drive falls below the level defined at F611 and remains there for the time set
at F612.
Direct Access Number F610
Parameter TypeCheck Box
Factory DefaultDisabled
Changeable During Run — No