H7 ASD Operation Manual 157
Low Current Trip Threshold
Program
Protection Parameters
Low Current Settings
When the low-current monitor is enabled, this function sets the low-current trip
threshold. The threshold value is entered as a percentage of the maximum rating
of the drive.
Direct Access Number F611
Parameter Type Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 100.0
Units — %
Low Current Trip Threshold Time
Program
Protection Parameters
Low Current Settings
When the low-current monitor is enabled, this function sets the time that the
low-current condition must exist to cause a trip.
Direct Access Number F612
Parameter Type Numerical
Factory Default 0
Changeable During Run — Ye s
Minimum — 0
Maximum — 255
Units — Seconds
Short Circuit Test
Program
Protection Parameters
Arm Short Check Settings
This parameter determines when the system will perform an Output Short
Circuit test.
Settings:
Every Run
Every Powerup
Direct Access Number F613
Parameter Type Selection List
Factory Default Every Run
Changeable During Run — No
Short Circuit Test Duration
Program
Protection Parameters
Arm Short Check Settings
This parameter sets the pulse width of the output pulse that is applied to the
ASD output during an Output Short Circuit test.
Direct Access Number F614
Parameter Type Numerical
Factory Default — (drive dependent)
Changeable During Run — No
Minimum — 1
Maximum — 100
Units — µS
Overtorque Trip
Program
Protection Parameters
Overtorque Parameters
This parameter Enables/Disables the Over Torque Tripping function.
When enabled, the ASD trips if a torque larger than the setting of F616 or F617
exists for a time longer than the setting of F618.
When disabled, the ASD does not trip due to overtorque conditions.
Direct Access Number F615
Parameter Type Check Box
Factory Default Disabled
Changeable During Run — No
F611 F615
www . ElectricalPartManuals . com