H7 ASD Operation Manual 163
Frequency Override Additive Input
Program
⇒
Feedback Parameters
⇒
Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed Output Frequency.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
LED Keypad (option)
Binary/BCD Input
Common Serial (TTL)
RS232/485
Communication Card
Motorized Pot
Pulse Input 1
Direct Access Number — F660
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Frequency Override Multiplying Input
Program
⇒
Feedback Parameters
⇒
Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the programmed Output Frequency.
If operating using the LED Keypad Option and Setting is selected, the value
entered at F729 is used as the multiplier.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
Setting (LED Keypad Option Only)
Direct Access Number — F661
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F660 F661