H7 ASD Operation Manual 167
Stop Pattern
No path available (Direct Access Only)
While operating using the LED Keypad Option the Stop Pattern parameter
determines the method used to stop the motor when the stop command is issued
via a Stop command from the LED Keypad.
The Decel Stop setting enables the Dynamic Braking system that is setup at
F304 or the DC Injection Braking system that is setup at F250, F251, and
F252.
The Coast Stop setting allows the motor to stop at the rate allowed by the
inertia of the load.
Settings:
Decel Stop
Coast Stop
Note:The Stop Pattern setting has no effect on the Emergency Off settings of
F603.
If using the LCD EOI, press ESC from the Frequency Command
screen to access this parameter.
Direct Access Number — F721
Parameter Type — Selection List
Factory Default — Decel Stop
Changeable During Run — Ye s
Torque Limit Group
No path available (Direct Access Only)
While operating using the LED Keypad Option this parameter is used to select
1 of 4 preset positive torque limits to apply to the active motor. The settings of
profiles 1 – 4 may be setup at F441, F444, F446, and F448, respectively.
Note: If using the LCD EOI, press ESC from the Frequency Command screen
to access this parameter.
Direct Access Number — F723
Parameter Type — Selection List
Factory Default — 1
Changeable During Run — Ye s
Feedback in Panel Mode
No path available (Direct Access Only)
While operating using the LED Keypad Option this parameter Enables/
Disables PID feedback control.
Note: If using the LCD EOI, press ESC from the Frequency Command screen
to access this parameter.
Direct Access Number — F724
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Ye s
LED Option Override Multiplication Gain
Program
⇒
Feedback Parameters
⇒
Override Control
If operating using the LED Keypad Option this parameter provides a value to
be used in the event that Setting is selected for the Frequency Override
Multiplying Input (F661).
Direct Access Number — F729
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — -100.00
Maximum — 100.00
F721 F729