168 H7 ASD Operation Manual
Communication Baud Rate (logic)
Program
Communication Setting Parameters
Communication
Settings
This parameter plays a role in the setup of the communications network by
establishing the Baud Rate of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Direct Access Number F800
Parameter TypeNumerical
Factory Default9600
Changeable During Run — Yes
Minimum — 1200
Maximum — 9600
Units — BPS
Parity
Program
Communication Setting Parameters
Communication
Settings
This parameter plays a role in the setup of the communications network by
establishing the Parity setting of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Settings:
No Parity
Even Parity
Odd Parity
Direct Access Number F801
Parameter TypeSelection List
Factory DefaultEven Parity
Changeable During Run — Yes
ASD Number
Program
Communication Setting Parameters
Communication
Settings
This parameter plays a role in the setup of the communications network by
assigning an identification (ID) number to each ASD in the communications
network.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Direct Access Number F802
Parameter TypeNumerical
Factory Default0
Changeable During Run — Yes
Minimum — 0
Maximum255
RS485 Communications Time Out Time (RS485)
Program
Communication Setting Parameters
Communication
Settings
This parameter plays a role in the setup of the communications network by
setting the time that no activity may exist over the communications link before
the link is severed (Time Out).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Direct Access Number F803
Parameter TypeNumerical
Factory Default0
Changeable During Run — Yes
Minimum — 0
Maximum100
Units — Seconds
F800 F803