208 Appendix F H7 ASD Operation Manual
Appendix F
Link Reactor Information
Selection of a link reactor (DCL) is often application specific. This document will provide guidelines for
selecting link reactors for the H7 series of drives.
The 600 Volt series drives above 15 HP allow for the reactor to be mounted internal to the drive. All other
H7 drives require that the DCL be mounted externally.
When selecting and mounting an external DCL, the air flow around the reactor, the thermal capability of
the reactor, the allowable voltage loss, and the amount of harmonic reduction required will be
considerations.
Table 17. DCL Selection Table.
Model Number
VT130H7U
DCL Part
Number
DCL Inductance
(mH)
DCL
(Amps)
2080 36350 0.40 30.0
2110 36351 0.30 38.0
2160 36376 0.20 57.0
2220 36353 0.20 76.0
2270 36355 0.10 114
4110 36358 1.30 20.0
4160 36359 0.90 29.0
4220 36360 0.70 39.0
4270 36361 0.50 50.0
4330 36363 0.40 75.0
4400 36364 0.30 88.0
4500 36365 0.20 114
4600 36365 0.20 114
4750A 36366 0.20 141
410KA 42769 0.14 205
6060 36356 2.50 11.0
6120 36359 0.90 29.0
6160 36359 0.90 29.0
6220 36360 0.70 39.0
6270 36362 0.50 55.0
6330 36361 0.50 50.0
6400 36363 0.40 75.0
6500 36363 0.40 75.0
6600 36364 0.30 88.0