H7 ASD Operation Manual 31
Panel Menu
The Panel menu may be accessed in either of two ways: while operating using the LED Keypad Option
the Panel menu may be accessed via F008 or if operating in the Local mode using the LCD EOI press
ESC from the Frequency Command screen to access the Panel menu.
The control settings of the Panel menu are effective for the LED keypad only if accessed via the Direct
Access method and are effective for the LCD EOI only if accessed via the Frequency Command screen.
Changes made to either of the Panel menus are not carried over to the other Panel menu.
Using either method provides quick access to the following Panel menu parameters:
Direction — Forward or Reverse (see F008 for further information on this setting).
Stop Pattern — The Decel Stop or Coast Stop settings determines the method used to stop the motor
when using the Stop|Reset key of the EOI. The Decel Stop setting enables the Dynamic Braking
system setup at F304 or the DC Injection Braking system setup at F250, F251, and F252. The Coast
Stop setting allows the motor to stop at the rate allowed by the inertia of the load.
Note: The Stop Pattern setting has no effect on the Emergency Off settings of F603.
V/f Group — 1 of 4 V/f profiles may be selected and run. Each V/f profile is comprised of 4 user
settings: Base Frequency, Base Frequency Voltage, Manual Torque Boost, and Electronic
Thermal Protection. Expanded descriptions of these parameters may be found in the section titled
Direct Access Parameter Information on pg. 48.
Accel/Decel Group — 1 of 4 Accel/Decel profiles may be selected and run. Each of the Accel/Decel
profiles is comprised of 3 user settings: Acceleration, Deceleration, and Pattern. Expanded
descriptions of these parameters may be found in the section titled Direct Access Parameter
Information on pg. 48 (or see F009 at the EOI).
Feedback in Panel Mode — This feature enables or disables the PID feedback function.
Torque Limit Group — This parameter is used to select 1 of 4 preset positive torque limits to apply
to the active motor (of a multiple motor configuration). The settings of profiles 1 – 4 may be setup at
F441, F444, F446, and F448, respectively.