H7 ASD Operation Manual 57
Preset Speed #6
Program
Pattern Run Control
Preset Speeds
6
This parameter assigns an output frequency to binary number 0110 and is
identified as Preset Speed #6. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see F018 for further
information on this parameter).
Direct Access Number F023
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #7
Program
Pattern Run Control
Preset Speeds
7
This parameter assigns an output frequency to binary number 0111 and is
identified as Preset Speed #7. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see F018 for further
information on this parameter).
Direct Access Number F024
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Low Speed Signal Output Frequency
Program
Terminal Selection Parameters
Reach Settings
The Low Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal so long as the ASD output
is at or below this setting (see Table 7 on pg. 72 for the available output
assignments).
Direct Access Number F100
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
Speed Reach Frequency
Program
Terminal Selection Parameters
Reach Settings
The Speed Reach Frequency sets a frequency threshold that, when reached or
is within the bandwidth specified by parameter F102, will provide a signal at an
output terminal that can close an appropriately configured output contact (see
Table 7 on pg. 72 for the available output assignments).
Direct Access Number F101
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
F023 F101