H7 ASD Operation Manual 59
ST Signal Selection
Program
Terminal Selection Parameters
Input Special Functions
This parameter is used to set the operation of the Standby (ST) control terminal
or any terminal configured as the ST terminal.
Settings:
ST-to-CC Required
ST-to-CC Not Required
Interlock with F/R Terminal
The setting ST-to-CC Required enables the ASD for operation so long as the
control terminal ST is connected to CC via a jumper, contact, or other means.
The ST-to-CC Not Required setting allows the ASD to operate without the
ST-to-CC connection. The control terminal ST may be configured for other
functions.
The Interlock with F/R Terminal setting configures the F (Forward) and R
(Reverse) control terminals for the secondary function of Standby. Closing a
set of contacts to either F or R will cause the ASD to accelerate the motor to the
programmed setpoint of F or R. Opening the F and R contact will disable the
ASD and the motor will coast to a stop. The control terminal ST may be
configured for other functions.
Direct Access Number F103
Parameter TypeSelection List
Factory DefaultST – CC Required
Changeable During Run — No
F103 F103