H7 ASD Operation Manual 75
OUT5 On Delay
Program
Terminal Selection Parameters
Output Terminal Delays
OUT5
This parameter delays the closing of the OUT5 output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
Direct Access Number F154
Parameter TypeNumerical
Factory Default2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT6 On Delay
Program
Terminal Selection Parameters
Output Terminal Delays
OUT6
This parameter delays the closing of the OUT6 output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
Direct Access Number F155
Parameter TypeNumerical
Factory Default2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT7 On Delay
Program
Terminal Selection Parameters
Output Terminal Delays
OUT7
This parameter delays the closing of the OUT7 output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
Direct Access Number F156
Parameter TypeNumerical
Factory Default2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT1 Off Delay
Program
Terminal Selection Parameters
Output Terminal Delays
OUT1
This parameter delays the opening of the OUT1 (A & C) output terminals by
the programmed value.
The delay may be increased to allow the devices that are connected to OUT1 to
respond.
Direct Access Number F160
Parameter TypeNumerical
Factory Default2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
F154 F160
www . ElectricalPartManuals . com