H7 ASD Operation Manual 81
Custom V/f Five-Point Setting #1 Voltage
Program
⇒
Special Control Parameters
⇒
V/f Five-Point Setting
The Custom V/f Five-Point Setting #1 Voltage establishes the percentage of
the output voltage that is to be associated with the frequency setting of F190
(Custom V/f Five-Point Setting #1 Frequency).
See F190 for additional information on custom V/f curves.
Direct Access Number — F191
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Custom V/f Five-Point Setting #2 Frequency
Program
⇒
Special Control Parameters
⇒
V/f Five-Point Setting
The Custom V/f Five Point Setting #2 Frequency sets the frequency to be
associated with parameter F193 (Custom V/f Five Point Setting #2 Voltage).
See F190 for additional information on custom V/f curves.
Direct Access Number — F192
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 400
Units — Hz
Custom V/f Five-Point Setting #2 Voltage
Program
⇒
Special Control Parameters
⇒
V/f Five-Point Setting
The Custom V/f Five-Point Setting #2 Voltage establishes the percentage of
the output voltage that is to be associated with the frequency setting of F192
(Custom V/f Five Point Setting #2 Frequency).
See F190 for additional information on custom V/f curves.
Direct Access Number — F193
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Custom V/f Five-Point Setting #3 Frequency
Program
⇒
Special Control Parameters
⇒
V/f Five-Point Setting
The Custom V/f Five Point Setting #3 Frequency sets the frequency to be
associated with parameter F195 (Custom V/f Five Point Setting #3 Voltage).
See F190 for additional information on custom V/f curves.
Direct Access Number — F194
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 400
Units — Hz
Custom V/f Five-Point Setting #3 Voltage
Program
⇒
Special Control Parameters
⇒
V/f Five-Point Setting
The Custom V/f Five-Point Setting #3 Voltage establishes the percentage of
the output voltage that is to be associated with the frequency setting of F194
(Custom V/f Five Point Setting #3 Frequency).
See F190 for additional information on custom V/f curves.
Direct Access Number — F195
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
F191 F195
www . ElectricalPartManuals . com