H7 ASD Operation Manual 89
RR Speed Reference Setpoint #1 (frequency)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control
mode.
See F210 for further information on this setting.
This parameter sets the RR Speed Reference Setpoint #1 (frequency) and is
the frequency that is associated with the setting of F210.
Direct Access Number F211
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — Hz
RR Speed Reference Setpoint #2 (%)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control or
the Torque Control mode.
See F210 for further information on this setting.
This parameter sets the RR input level that represents RR Reference Setpoint
#2 (frequency) (torque or frequency). This value is entered as 0 – 100% of the
0 – 10 VDC RR input signal range.
Direct Access Number F212
Parameter TypeNumerical
Factory Default100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
RR Speed Reference Setpoint #2 (frequency)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control
mode.
See F210 for further information on this setting.
This parameter sets RR Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of F212.
Direct Access Number F213
Parameter TypeNumerical
Factory Default80.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — Hz
RR Torque Reference Setpoint #1 (%)
Program
Torque Setting Parameters
Setpoints
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Torque Control
mode.
This is accomplished by establishing an associated V/f output pattern for a given
RR input level and motor load.
See F210 for further information on this setting.
This parameter sets RR Torque Reference Setpoint #1 and is the output torque
value that is associated with setting of F210. This value is entered as 0 – 250%
of the rated torque.
Direct Access Number F214
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 250.0
Units — %
F211 F214