EasyManua.ls Logo

Toshiba H9 ASD - Analog Input Filter

Toshiba H9 ASD
286 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H9 ASD Installation and Operation Manual 109
Analog Input Filter
Program Frequency Analog Filter
Analog filtering is applied after the analog reference signal is converted to a
digital signal. The type of filtering used is Rolling Average over time.
Settings:
0 — None (1 mS)
1 — Small (8 mS)
2 — Medium (16 mS)
3 — Large (32 mS)
4 — Huge (64 mS)
The analog input signal is sampled and converted to a digital signal. With no
filtering applied, the resulting digital value is scaled for use by the
microprocessor of the ASD.
If the filtering selection Small is selected, the ASD averages the last 8 mS of
sampled signal and converted (digital) values. The rolling average is updated
(every 4 µS) and scaled for use by the microprocessor.
This holds true for the Medium, Large, and Huge selections providing a larger
sample to produce the average for use by the microprocessor.
False responses to electrical noise are eliminated with no loss in bandwidth
because the value used by the drive is the average value of several samples.
Direct Access Number — F209
Parameter Type — Selection List
Factory Default — None
Changeable During Run — Ye s
F209 F209
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net